1. product introduction
The TYGB Integrated type Vortex flowmeter with temperature & pressure compensation adopted new design concept, collecting temperature, pressure and flow rate signal in a body. Through intelligent digital processor to output compensated standard flow after the processed three mixed signal, which come true the temperature and pressure compensation for gas and steam. Because of using the intelligent integration design concept, this series Flowmeter has the advantages of compact structure and easy to install and maintenance.
2. Functions and features
2.1 body of table can have the temperature and pressure compensation functions at the same time, can measure the Stdvol-flow or standard mass flow of the fluid.
2.2 all intelligent and digital designed, can compensate the measured fluid flow rate or standard mass flow automatic.
2.3 A brand new digital filter and fixed function makes the flow measurement more accuracy and reliable.
2.4 The battery type can continuous working for more than two years without the external power source.
2.5 New dot matrix Chinese character LCD display, so that the operation is more convenient.
3. The key technical indexes
inside nominal diameter (mm) | 25,40,50,65,80,100,125,150,200,250,300,(300~1000plug-in) |
nominal pressure (MPa) | DN25-DN200 4.0(>4.0 order by agreement),DN250-DN300 1.6(>1.6 order by agreement) |
medium temperature (℃) | piezoelectric type:-40~260,-40~320;capacitance:-40~300, -40~400,-40~450(order by agreement) |
noumenon | 1Cr18Ni9Ti,(order by agreement if need other material) |
vibrating acceleration | piezoelectric type:0.2g capacitance:1.0~2.0g |
range | ±1%R,±1.5%R,±1FS;plug-in:±2.5%R,±2.5%FS |
Range degree | 1:6~1:30 |
service voltage | sensor:+12V DC,+24V DC;transmitter:+12V DC ,+24V DC;battery supply feed:3.6Vbattery |
output signal | square wavepulse (non- battery supply feed):high level≥5V,low level≤1V;current:4~20mA |
loss coefficient | JB/T9249 Cd≤2.4 |
anti-explosion sign | Ben-an type:ExdⅡia CT2-T5 anti-explosion type:ExdⅡCT2-T5 |
Protection grade | ordinary type IP65 dive type IP68 |
environment condition | Tem-20℃~55℃,relative humidity 5%~90%,atm press 86~106kPa |
medium | gas、liquid、vapor |
transmission range | three-wire system flow sensor:≤300m,electric sign of two-wire system transmitter(4~20mA):load resistance≤750Ω |
4. Design & installation for meter and ensuring caliber
4.1.When tested gas is vapor,often use quality flow as unit of measurement quality flow,as:t/h or Kg/h. because of vapor(overheating & saturated), density would be changed under different temp & press,so to ensure the flow range, see (8) formula(8)
TIPS:
ρ:density of vapor(kg/m3)
ρ0:1.205kg/m3
Q蒸汽 :quality flow of vapor(t/h)
4.2.For pressure loss, check the effect of pressure loss to craft pipeline,(Unit:Pa):
Δp= CdρV2/2 formula(9)
Tips:
Ρ: density of medium under working condition(kg/m3)V: mean flow rate(m/s)
4.3.If tested medium is liquid, to avoid 为gasification and loss, shall make the press of pipeline as follow:
p≥2.7Δp+1.3p0 formula(10)
Tips:
Δp: pressure loss(Pa)
p0:saturated vapor pressure of liquid which under working temperature.
(Pa absolute pressure)
Po: fluidic vapor pressure
(Pa absolute pressure)
4.4.vortex street flow meter is not suitable for testing high viscosity liquid. if counted measurable lower limit flow is not suitable for designing, pls select and use other meter type..
4.5. If as the counted parameter, the two or more kinds of meter can be used, then use less caliber, cheaper. Tips: as far as possible tested range during upper limit of about 1/2~2/3.
5. Model selection table of vortex street flow meter(JB/T9294-1999 standard)
1.Model selection table of sensor
Model selection for TYGB series vortex street meter
Model chart | Describing | ||||||||||||||||||||
TY | vortex street meter | ||||||||||||||||||||
G | sensor | ||||||||||||||||||||
TEST WAY | B | piezoelectric transducer | |||||||||||||||||||
E | Capacitance sensor | ||||||||||||||||||||
Joint way | 1 | full package type | flanged joint type | ||||||||||||||||||
2 | full package type | flanged installing type | |||||||||||||||||||
3 | plug-in type | simple plug-in | |||||||||||||||||||
4 | plug-in type | ball valve plug-in | |||||||||||||||||||
Test medium | 2 | liquid | |||||||||||||||||||
3 | gas | ||||||||||||||||||||
4 | vapor | ||||||||||||||||||||
inside nominal diameter |
02 … 30 |
DN25 unit:mm DN300 |
|||||||||||||||||||
service environment | P | ordinary type | |||||||||||||||||||
B | explosion proof type | ||||||||||||||||||||
output signal | 1 | output pulse | |||||||||||||||||||
2 | 4~20mA current output,liquid-crystal display | ||||||||||||||||||||
3 | RS-485 communication | ||||||||||||||||||||
4 | battery supply feed, without Temp、get pressure | ||||||||||||||||||||
5 | Tem-pre system,4~20mA current output type | ||||||||||||||||||||
6 | Tem-pre system,battery supply feed type | ||||||||||||||||||||
model selection | e.g.:TYGB2405-P2 full package type capacitance vortex street meter,flanged installing type joint,medium is vapor drift diameter of meter is DN50, ordinary 4~20mA current signal output |
Target Flowmeter/Functional Unified Fixed Ultrasonic Flowmeter/Handheld Ultrasonic Flowmeter/ Ultrasonic Flow Module/Portable Ultrasonic Flowmeter/Separate Fixed Ultrasonic Flowmeter/Insertion type Electromagnetic Flowmeter/ Battery powered Electromagnetic Flowmeter/ Remote Type electromagnetic Flowmeter/ TYLD Flanged Electromagnetic Flowmeter/Clamped Electromagnetic Flowmeter/ Metal Tube Float Flowmeter/ Verabar of the Flowmeter/ Insertion Vortex Street Meter/ Integrated Vortex Flowmeter with Temperature & Pressure Compensation/ Intelligent Vortex Flowmeter/ Gas Turbine Flowmeter/ Liquid Turbine Flowmeter/Thermal Gas Mass Flowmeter/ Coriolis Mass Flowmeter/LFX rotor steam Flowmeter/ LUXB liquid precession vortex Flowmeter/ Cross section Flowmeter/ FP-64B balanced dual-chamber container/ LG series throttling device/Integral differential pressure flowmeter/LC Oval gear flowmeter/V Cone Flowmeter/LGBA Annubar Flowmeter/ LGBD Delta Flowmeter/3151 on-line densimeter