Flowmeter
Pressure Transmitter
Level Measurement
YTC Control Valve Accessories
HKC Automation Controls
ABB Valve Positioner
Mass Flow Controller
Doppler Current Meter
Pressure Switch
Yokogawa Flowmeter
Digital Pressure Gauge
Pressure Sources
Newsletter
for wholesale
about the latest offers and deals Subscribe today!

KSP high pressure controller
The mark of anti-explosion is ExedllCT6 and suit for gas, liquid, or steam and medium IIA IIB IIC T1~T6 explosive mixture which has corrosion effect and achieve automatic control.
Description

  1. Product introduction

  This series of products using leak-off piston/rubber diaphragm sensor components,ordinary type suit for gas, liquid and steam which has no corrosion effect and achieve automatic control,Controller set point is adjustable,The range is 1~40MPa,the adjusting range is 15%~ 95%. The quantity of this switch almost is 1Kg.

  The mark of anti-explosion is ExedllCT6 and suit for gas, liquid, or steam and medium IIA IIB IIC T1~T6 explosive mixture which has corrosion effect and achieve automatic control.

  If you adopt window type, please give instructions before you buy it, the window type number is KSPC dead zone cannot be adjustable, and KSPA dead zone can be adjustable series.

  Single pole double throw switch process:

  Wiring terminal C-NO: the raise of pressure till changeable value ON;

  wiring terminal C-NC:the raise of pressure till changeable value OFF.

  2.Main technical specification

  Ordinary type Anti-explosion
Working viscosity ≤10-3m2/s ≤10-3m2/s
Switch element micro switch micro switch
Range of anti-explosion / EXedIICT6 NO.320110395
Range of shell protection IP67 IP67
Environment temperature -25℃~80℃ -25℃~80℃
Environment humility 5%~95% 5%~95%
Life span 105 times circle 105 times circle
Anti-earthquake <Max . 2g <Max . 2g
Contact capacity Vmax=380V  Imax=15A Vmax=380V  Imax=15A
Repeatability error ≤1.0% ≤1.0%

  3.Scale range table

Range code Range Dead zone Switching frequency Sensor material
The piston transducer Rubber diaphragm sensor
HG10 KG10 1—10MPa 0.4MPa 20times/min According to the range code of sensor selection
 
HG16 KG16 1—16MPa 0.5MPa 20times/min
HG25 KG25 2—25MPa 0.6MPa 20times/min
HG40 KG40 2—40MPa 0.8MPa 20times/min
The maximum working pressure:40MPa   Withstand pressure:60MPa

Chinese Pressure Switch
Diaphragm controller/Diaphragm Differential Pressure Switch/Diaphragm Pressure Switch/Diaphragm type-Diaphragm pressure switch/Diaphragm vacuum switch/KSC - II Intelligent differential pressure controller/KSC Micro differential pressure  Differential pressure controller/KSP - II Intelligent pressure controller/KSP High pressure controller/KSP High pressure controller/KSP Micro pressure controller/KSP Pressure controller/KSP(W)Pressure type temperature controller/KTPL Intelligent pressure switch/ KTPS Intelligent liquid level switch/ KTPW Intelligent temperature switch/KTL Intelligent pressure switch/KTS Intelligent liquid level switch/KTW Intelligent temperature switch/KSP-I Intelligent pressure controller/KSPZ Series digital temperature controller/KSV Micro negative pressure controller/KSV Negative pressure controller/KTPJ Economical pressure switch
 
 
United States KFT
KTC Differential pressure switch/KTC Explosion-proof differential pressure switch/KTP Double contact independently adjustable pressure switch/KTP Double contact pressure switch/KTP Explosion-proof pressure switch/KTP Mirco pressure switch/KTP Pressure switch/KTPV Vaccum pressure switch/KTPW Pressure type temperature switch