1、The features
Yokogawa EJA120A tiny differential pressure transmitter used to measure tiny differential pressure, and then transform it into a 4-20 current signal output. Yokogawa EJA120A differential pressure transmitter can communication with BRAIN hand operator or CENTUM CS/muXL or Rosemount HART 475 operator each other, through them to set and monitor, etc.
Application | Stype | Model | capsule | Measuremene (KPa) | The maximum pressure (Kpa) |
Tiny Differential | Normal installation | EJA120A | E | 0.1-1 | 50 |
EJA120A micro differential pressure transmitter | ||
Ediaphragm capsule | ||
MeasurementRange | -1~1kPa(-4~4inH2O) | |
Measurement Span | 0.1~1kPa(0.4~4inH2O) | |
Accuracy | ±0.2% | |
Protection Level | IP67,NEMA 4X,JIS C0920 The immersion type | |
Explosion-proof | FM,CENELEC ATEX,CSA,IECEx | |
Output Signal | 4~20mA DC or FOUNDATION™ fieldbus PROFIBUS PA two wire system of digital communication | |
Power |
BRAI and HART:10.5~42V DC (intrinsic safety type: 10.5~30V DC) Fieldbus:9~32V DC (intrinsic safety typeEntitym model9~24V DC,intrinsic safety typeFISCO model9~17.5V DC) |
|
Environment Temperature | -25~80℃(-13~176℉) | |
Process Temperature | -25~80℃(-13~176℉) | |
Maximum Pressure | 50kPa (7.25psi) | |
Installation | 2-inchflange installation | |
Walled Parts Materials | diaphragm capsule | SUS316L(HastelloyC-276) |
Cover flange | SUS316 | |
Shell | Aluminum alloy or SUS316 stainless steel (optional) |
Output signal |
|
||||||||||||||||||
-G | Digital communication (PROFIBUS PA protocol, refer to GS 01C22T03-00E) | ||||||||||||||||||
Measurement
span (capsule)
|
|
||||||||||||||||||
Wetted parts
material*6
|
|
||||||||||||||||||
Process connections |
|
||||||||||||||||||
Bolts and nuts material |
|
||||||||||||||||||
Installation |
|
||||||||||||||||||
Electrical connection |
|
||||||||||||||||||
A | G1/2 female, two electrical connections and a SUS316 blind plug | ||||||||||||||||||
C | 1/2 NPT female, two electrical connections and a SUS316 blind plug | ||||||||||||||||||
D | M20 female, two electrical connections and a SUS316 blind plug | ||||||||||||||||||
Integral indicator |
|
||||||||||||||||||
Mounting bracket |
|
||||||||||||||||||
K | SUS316 2-inch pipe mounting (L type) | ||||||||||||||||||
N | (None) |
The ‘☆’marks indicate the most typical selection for each specification. Example: EJA120A-DES5A-92NA/
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use ofSUS316 material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
*1:Indicates cover flange and process connector material.
*2:Diaphragm material is Hastelloy C-276 or ASTM N10276. Other capsule wetted parts materials are SUSF316L,SUS316L or ASTM grade 316L.
*3:If necessary, specify Mounting bracket code C or D.
*4:If necessary, specify Mounting bracket code A or B.
*5:Not applicable for Output signal code F and G.
*6:Users must consider the characteristics of selected wetted parts material and the influence of process fluids.The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid can contaminate the user's process fluids.Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide,sodium hypochlorite, and high-temperature steam (150 °C [302 °F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*7:SUS316 or ASTM grade 316.
EJA110A Differential pressure transmitter/EJA118W/EJA118Y/EJA118N Double flanges differential pressure transmitter/EJA120A micro differential pressure transmitter/ EJA130A High performance differential pressure transmitter/EJA210A/EJA220A Flange Mounted Differential Pressure Transmitter/ EJA310A Absolute Pressure Transmitter/ EJA430A Gauge Pressure Transmitter/ EJA438W and EJA438N Diaphragm Sealed Gauge Pressure Transmitters/ Model EJA440A High Pressure Transmitter/EJA510A and EJA530A Absolute and Gauge Pressure Transmitters/Model EJX110A Differential pressure transmitter/EJX118W Diaphragm Sealed Differential Pressure Transmitters/EJX210A Flange Mounted Differential Pressure Transmitter/EJX430A Gauge pressure transmitter/ EJX438A Diaphragm seal pressure transmitter/EJX910A Multivariable Pressure Transmitter