1、The features
Yokogawa EJA 510A absolute pressure transmitter / 530A pressure transmitter Yokogawa EJA510A Absolute pressure transmitter and yokogawa EJA530A pressure transmitter is used to measure the pressure of gas, liquid and steam, then transform it into a 4-20 madc current signal output. Yokogawa EJA510A pressure transmitter and pressure transmitter yokogawa EJA530A can also through the BRAIN hand operator or CENTUM CS/muXL or rosemount HART 475 hand operator to communicate with each other, through them to set and monitor, etc.
2、Technical specifications
EJA510A / EJA530AAbsolute and Gauge Pressure Transmitters | |||||
A capsule | B capsule | C capsule | D capsule | ||
Measurement span |
0~200kPa (0~29psi) |
0~2MPa (0~290psi) |
0~10MPa (0~1450psi) |
0~50MPa (0~7200psi) |
|
Measurement range |
10~200kPa (1.45~29psi) |
0.1~2MPa (14.5~290psi) |
0.5~10MPa (72.5~1450psi) |
5~50MPa (720~7200psi) |
|
Accuracy | ±0.2% | ±0.2% | ±0.2% | ±0.2% | |
Level of Protection | IP67,NEMA 4X,JIS C0920 The immersion type | ||||
explosion-proof | FM,CENELEC ATEX,CSA,IECEx | ||||
Output Signal | 4~20mA DC or FOUNDATION™ fieldbus PROFIBUS PA two wire system of digital communication | ||||
Power |
BRAI and HART:10.5~42V DC (intrinsic safety type: 10.5~30V DC) Fieldbus:9~32V DC (intrinsic safety typeEntitym model9~24V DC,intrinsic safety typeFISCO model9~17.5V DC) |
||||
Environment Temperature |
-40~85℃(-40~185℉) (normal) -30~80℃(-22~176℉) (Integral indicator) |
||||
Process Temperature | -40~120℃(-40~248℉) (Normal) | ||||
The maximum pressure | 4.5MPa (645psig) | The maximum pressure | 4.5MPa (645psig) | The maximum pressure | |
Installation | 2-inch Pipe installation | ||||
Wetted parts materials | diaphragm capsule | Wetted parts materials | |||
Cover flange | |||||
Shell | Aluminum alloy or SUS316 stainless steel (optional) |
3、Product selection list:
Basic specification code: EJA510A-DAS4N-02NN
EJA510A---- Absolute pressure transmitter
EJA530A---- Gauge pressure transmitter
Output Signal |
|
||||||||||||||||||
-F | Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C22T02-00E) | ||||||||||||||||||
-G | Digital communication (PROFIBUS PA protocol, refer to GS 01C22T03-00E) | ||||||||||||||||||
Measurement span
(capsule)
|
|
||||||||||||||||||
Wetted parts
material *2
|
|
||||||||||||||||||
Process connection
|
|
||||||||||||||||||
- |
|
||||||||||||||||||
- |
|
||||||||||||||||||
Electrical connection |
|
||||||||||||||||||
A | G1/2 female, two electrical connections and a SUS316 blind plug | ||||||||||||||||||
C | 1/2 NPT female, two electrical connections and a SUS316 blind plug | ||||||||||||||||||
D | M20 female, two electrical connections and a SUS316 blind plug | ||||||||||||||||||
Integral indicator |
|
||||||||||||||||||
Mounting bracket |
|
The ‘☆’ marks indicate the most typical selection for each specification. Example: EJA530A-DAS4N-02NN/
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use ofSUS316 material,there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
1、Not applicable for Output signal code F and G.
2、Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personneland/or damage to plant facilities. It is also possible that the diaphragm itself can be damaged and that material fromthe broken diaphragm and the fill fluid can contaminate the user's process fluids.Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide,sodium hypochlorite, and high-temperature steam (150 ° C [302 ° F] or above). Contact Yokogawa for detailedinformation of the wetted parts material.
3、Hastelloy C-276 or ASTM N10276.
4、SUS316L or ASTM grade 316L.
EJA110A Differential pressure transmitter/EJA118W/EJA118Y/EJA118N Double flanges differential pressure transmitter/EJA120A micro differential pressure transmitter/ EJA130A High performance differential pressure transmitter/EJA210A/EJA220A Flange Mounted Differential Pressure Transmitter/ EJA310A Absolute Pressure Transmitter/ EJA430A Gauge Pressure Transmitter/ EJA438W and EJA438N Diaphragm Sealed Gauge Pressure Transmitters/ Model EJA440A High Pressure Transmitter/EJA510A and EJA530A Absolute and Gauge Pressure Transmitters/Model EJX110A Differential pressure transmitter/EJX118W Diaphragm Sealed Differential Pressure Transmitters/EJX210A Flange Mounted Differential Pressure Transmitter/EJX430A Gauge pressure transmitter/ EJX438A Diaphragm seal pressure transmitter/EJX910A Multivariable Pressure Transmitter